Type | AC power supply models | DC power supply models |
Model | CP1E-@@@S@D@-A CP1E-@@@D@-A | CP1E-@@@S@D@-D CP1E-@@@D@-D |
Enclosure | Mounted in a panel | |
Dimensions (H × D × W) |
E/N/NA@@-type
CPU Unit with 10 I/O points (CP1E-E10D@–@): 90mm *1 × 85mm *2 × 66 mm CPU Unit with 14 or 20 I/O points (CP1E-@14D@–@/@20D@–@): 90mm *1 × 85mm *2 × 86 mm CPU Unit with 30 I/O points (CP1E-@30D@–@): 90mm *1 × 85mm *2 × 130 mm CPU Unit with 40 I/O points (CP1E-@40D@–@): 90mm *1 × 85mm *2 × 150 mm CPU Unit with 60 I/O points (CP1E-N60D@–@): 90mm *1 × 85mm *2 × 195 mm CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D@–@): 90mm *1 × 85mm *2 × 130 mm E/N/@@S(1)-type CPU Unit with 14 or 20 I/O points (CP1E-@14SD@–@/@20SD@–@): 90mm *1 × 79mm *2 × 86 mm CPU Unit with 30 I/O points (CP1E-@30S(1)D@–@): 90mm *1 × 79mm *2 × 130 mm CPU Unit with 40 I/O points (CP1E-@40S(1)D@–@): 90mm *1 × 79mm *2 × 150 mm CPU Unit with 60 I/O points (CP1E-@60S(1)D@–@): 90mm *1 × 79mm *2 × 195 mm |
|
Weight |
CPU Unit with 10 I/O points (CP1E-E10D@–@): 300g max. CPU Unit with 14 I/O points (CP1E-@14(S)D@–@): 360g max. CPU Unit with 20 I/O points (CP1E-@20(S)D@–@): 370g max.
CPU Unit with 30 I/O points (CP1E-@30(S@)D@–@): 600g max. CPU Unit with 40 I/O points (CP1E-@40(S@)D@–@): 660g max. CPU Unit with 60 I/O points (CP1E-@60(S@)D@–@): 850g max. CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D@–@): 680g max. |
|
Supply voltage | 100 to 240 VAC 50/60 Hz | 24 VDC |
Operating voltage range | 85 to 264 VAC | 20.4 to 26.4 VDC |
Power consumption |
15 VA/100 VAC max.
25 VA/240 VAC max. (CP1E-E10D@-A/@14(S)D@-A/@20(S)D@-A) |
9 W max. (CP1E-E10D@-D)
13 W max. (CP1E-N14D@-D/N20D@-D) |
50 VA/100 VAC max.
70 VA/240 VAC max. (CP1E-NA20D@-A/@30(S@)D@-A/@40(S@)D@-A/ N60(S@)D@-A) |
20 W max.
(CP1E-NA20D@-D/N30(S@)D@-D/N40(S@)D@-D/ N60(S@)D@-D) *4 |
|
Inrush current |
120 VAC, 20 A for 8 ms max. for cold start at room temperature
240 VAC, 40 A for 8 ms max. for cold start at room temperature |
24 VDC, 30 A for 20 ms max. for cold start at room temperature |
External power supply *3 |
Not provided.
(CP1E-E10D@-A/@14(S)D@-A/@20(S)D@-A) 24 VDC, 300 mA (CP1E-NA20D@-A/@30D@-A/@40D@-A/@60D@-A/ @30SDR-A/@40SDR-A/@60SDR-A) |
Not provided |
Insulation resistance | 20 MΩ min. (at 500 VDC) between the external AC terminals and GR terminals | Except between DC primary current and DC secondary current |
Dielectric strength | 2,300 VAC 50/60Hz for 1 min between AC external and GR terminals Leakage current: 5 mA max. | Except between DC primary current and DC secondary current |
Ambient operating temperature | 0 to 55 °C | |
Ambient humidity | 10% to 90% | |
Atmosphere | No corrosive gas. | |
Ambient storage temperature | -20 to 75 °C (excluding battery) | |
Altitude | 2,000 m max. | |
Pollution degree | 2 or less: Meets IEC 61010-2-201. | |
Noise resistance | 2 kV on power supply line (Conforms to IEC61000-4-4.) | |
Overvoltage category | Category II: Meets IEC 61010-2-201. | |
EMC Immunity Level | Zone B | |
Vibration resistance | Conforms to JIS 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) |
|
Shock resistance | Conforms to JIS 60068-2-27.
147 m/s2, 3 times in X, Y, and Z directions |
|
Terminal block | Fixed (not removable) | |
Terminal screw size | M3 | |
Applicable standards | Conforms to EC Directive | |
Grounding method | Ground to 100 Ω or less. |