    Sensor

    Programmable Logic Controller KV-N24AR

    • Base Unit
    • AC power supply type
    • Input 14 points/output 10 points
    • Relay output
    Programmable Logic Controller KV-N24AR
     

    Model

    KV-N24AR

    General specifications

    Power voltage

    100 to 240 VAC (+10%/-15%)

    Operating ambient temperature

    0 to 55°C 32 to 131°F (no freezing)*1 *2

    Operating ambient humidity

    5 to 95% RH (no condensation)*1

    Operating environment

    As little dust and corrosive gas as possible

    Noise immunity

    1500 V peak-to-peak or more, pulse duration 1 μs, 50 ns (based on noise simulator), IEC standard compliant (IEC61000-4-2/3/4/6)

    Withstand voltage

    1500 VAC for 1 minute, between power supply terminal and I/O terminals and between all external terminals and case

    Insulation resistance

    50 MΩ or more (500 VDC megger used to perform measurements between power terminal and input terminals, and between all external terminals and case)

    Output power supply voltage

    24 VDC (±10%; output capacity: 0.6 A)

    Storage temperature

    −25 to +75°C −13 to +167°F

    Vibration resistance

    Intermittent vibration

    Frequency: 5 to 9 Hz

    Amplitude: 3.5 mm 0.14"*3*4

    Frequency: 9 to 150 Hz

    Acceleration: 9.8 m/s2 32.2'/s2*3*4

    Continuous vibration

    Frequency: 5 to 9 Hz

    Amplitude: 1.75 mm 0.07"*3*4

    Frequency: 9 to 150 Hz

    Acceleration: 4.9 m/s2 16.1'/s2*3*4

    Shock resistance

    Acceleration: 150 m/s2 492.1'/s2, application time: 11 ms, three times in each of the X, Y, and Z directions

    Operating altitude

    2000 m 6561.7' or less

    Overvoltage category

    AC: II, DC: I

    Pollution degree

    2

    Performance specifications

    Calculation control method

    Program storage method

    I/O control method

    Refresh method

    Program language

    Expanded ladder, KV Script, mnemonic

    Number of instructions

    Basic instruction: 81 types and 182 instructions, Application instruction: 39 types and 56 instructions, Calculation instruction: 123 types and 311 instructions, Expansion instruction: 92 types and 141 instructions, Total: 335 types and 690 instructions

    Instruction execution speed

    Basic instruction: 50 ns minimum, Application instruction: 170 ns minimum

    Program capacity

    8k steps

    Maximum number of attachable I/O units

    8

    Maximum number of I/O points

    256 (excluding the base unit I/O)

    Input relay/Output relay/Internal auxiliary relay

    R

    Total of 9600 points 1 bit (R000 to R59915)

    Link relay

    B

    8192 points 1 bit (B0 to B1FFF)

    Internal auxiliary relay

    MR

    9600 points 1 bit (MR000 to MR59915)

    Latch relay

    LR

    3200 points 1 bit (LR000 to LR19915)

    Control relay

    CR

    1440 points 1 bit (CR000 to CR8915)

    Timer

    T

    512 points 32 bit (T0 to T511)

    Counter

    C

    256 points 32 bit (C0 to C255)

    Data memory

    DM

    32768 points 16 bit (DM0 to DM32767)

    Link register

    W

    16384 points 16 bit (W0 to W3FFF)

    Temporary memory

    TM

    512 points 16 bit (TM0 to TM511)

    High-speed counter

    CTH

    2 points (CTH0 to CTH1), 32-bit automatic reset counter*5 (Input response: 100 kHz per single phase, 50 kHz per phase difference)*6

    High-speed counter comparator

    CTC

    4 points (CTC0 to CTC3), 32 bits, two points per high-speed counter

    Index register

    Z

    12 points 32 bit (Z01 to Z12)

    Control memory

    CM

    9000 points 16 bit (CM0 to CM8999)

    Base unit I/O

    Input: 14 points, output: 10 points, Input common: 1 point, Output common: 5 points

    Number of comments and labels that can be stored in the main unit

    Device comment

    20000
    When a maximum-length ladder program is written with no labels.

    Label

    28000
    When a maximum-length ladder program is written with no device comments.

    Power off hold function

    Program memory

    Flash ROM can be rewritten 10000 times

    Device

    Nonvolatile RAM*7

    Self-diagnosis function

    CPU error, RAM error, and other problems

    Input specifications

    Relay number

    General input: R000 to R003, R008 to R013 (10 points), High-speed A-phase and B-phase input: R004 to R007 (2 channels, 4 points in total)

    Input mode

    24 VDC input (open collector)

    Maximum input voltage

    26.4 VDC

    Rated input voltage

    24 VDC (General input: 5.3 mA, High-speed A-phase and B-phase input: 6.5 mA*8)

    Minimum ON voltage

    19 VDC

    Maximum OFF current

    1.5 mA

    Common method

    General input: All points/1 common (1 terminal), High-speed A-phase and B-phase input: Shared common for all points (shared with general input)

    Circuit delay time

    General input:
    OFF to ON: Max. 30 μs (Typ. 3.5 μs), ON to OFF: Max. 50 μs (Typ. 15 μs)
    High-speed A-phase and B-phase input:
    OFF to ON: Max. 2 μs (Typ. 1.1 μs), ON to OFF: Max. 2 μs (Typ. 0.3 μs)
    *9

    Input time constant

    Normal: 10 ms, When the HSP instruction is used: 10 μs
    When CR2305 is turned ON: 10 μs to 10 ms, eight-level switching is possible (set with CM1620). Can also be set from the Unit Editor.*9

    Input time constant setting 10 µs: Digital filter 1.6 to 2 µs
    Input time constant setting 20 µs: Digital filter 9 to 12 µs
    Input time constant setting 110 µs: Digital filter 90 to 93 µs
    Input time constant setting 500 µs: Digital filter 300 to 400 µs
    Input time constant setting 1 ms: Digital filter 800 to 900 µs
    Input time constant setting 2.5 ms: Digital filter 2.3 to 2.4 ms
    Input time constant setting 5 ms: Digital filter 4.0 to 4.5 ms
    Input time constant setting 10 ms: Digital filter 9 to 9.5 ms

    Response frequency

    (High-speed A-phase and B-phase input) Single phase: 100 kHz, phase difference: 50 kHz, 24 V ±10%, Duty 50%

    Output specifications

    Relay number

    R500 to R509 (10 points)

    Output mode

    Relay

    Rated load

    250 VAC/30 VDC, 2 A

    Common method

    2 to 4 points/1 common

    ON/OFF response time

    10 ms or less

    ON resistance

    50 mΩ or less

    Minimum applicable load

    100 μA/100 mVDC

    Relay life

    Electrical: 100000 cycles or more (20 cycles/minute), Mechanical: 20000000 cycles or more

    Relay replacement

    Impossible

    Built-in serial port

    Interface

    Communication standard

    RS-232C

    Connection

    Modular connector

    Transmission specifications RS-232C

    Baud rate

    1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps

    Transmission method

    Full duplex

    Data format

    Start bit

    1 bit

    Data bits

    7 bits, 8 bits

    Stop bits

    1 bit, 2 bits

    Error detection

    Parity

    Even, odd, none

    Transmission distance

    15 m 49.2'

    Number of transmission units

    1

    Indication

    SD (green), RD (red)

    Internal current consumption

    79 VA

    Weight

    Approx. 500 g

    *1 The range guaranteed as a system (excluding items specially noted for the units and cassettes).
    *2 The temperature below the unit center (30 mm 1.18") inside a control panel.
    *3 These specifications correspond to situations in which the unit is mounted on a DIN rail and in which the unit is mounted on the panel directly.
    *4 Conforms to JIS B 3502 and IEC61131-2, Scan times: 10 times (100 minutes) in each of the X, Y, and Z directions
    *5 You can also configure the settings so that automatic reset is not used.
    *6 Only open collectors are supported. Line drivers are not supported.
    *7 You can set the target device by clicking “CPU system setting” and then “Power off holding” in KV STUDIO.
    *8 Reference value of input current.
    *9 The input response time corresponding to the input time constant can be calculated as shown below. (Response time) = (Circuit delay of the input circuit) + (Delay by the digital filter)
    Example: Maximum response time when the input time constant is set to 500 μs
    OFF to ON: 30 μs (circuit delay) + 400 μs (digital filter) = 430 μs
    ON to OFF: 50 μs (circuit delay) + 400 μs (digital filter) = 450 μs


    Verification