Sensor
Programmable Logic Controller KV-N24AR
- Base Unit
- AC power supply type
- Input 14 points/output 10 points
- Relay output
Model |
KV-N24AR |
|||
General specifications |
Power voltage |
100 to 240 VAC (+10%/-15%) |
||
Operating ambient temperature |
0 to 55°C 32 to 131°F (no freezing)*1 *2 |
|||
Operating ambient humidity |
5 to 95% RH (no condensation)*1 |
|||
Operating environment |
As little dust and corrosive gas as possible |
|||
Noise immunity |
1500 V peak-to-peak or more, pulse duration 1 μs, 50 ns (based on noise simulator), IEC standard compliant (IEC61000-4-2/3/4/6) |
|||
Withstand voltage |
1500 VAC for 1 minute, between power supply terminal and I/O terminals and between all external terminals and case |
|||
Insulation resistance |
50 MΩ or more (500 VDC megger used to perform measurements between power terminal and input terminals, and between all external terminals and case) |
|||
Output power supply voltage |
24 VDC (±10%; output capacity: 0.6 A) |
|||
Storage temperature |
−25 to +75°C −13 to +167°F |
|||
Vibration resistance |
Intermittent vibration |
Frequency: 5 to 9 Hz |
Amplitude: 3.5 mm 0.14"*3*4 |
|
Frequency: 9 to 150 Hz |
Acceleration: 9.8 m/s2 32.2'/s2*3*4 |
|||
Continuous vibration |
Frequency: 5 to 9 Hz |
Amplitude: 1.75 mm 0.07"*3*4 |
||
Frequency: 9 to 150 Hz |
Acceleration: 4.9 m/s2 16.1'/s2*3*4 |
|||
Shock resistance |
Acceleration: 150 m/s2 492.1'/s2, application time: 11 ms, three times in each of the X, Y, and Z directions |
|||
Operating altitude |
2000 m 6561.7' or less |
|||
Overvoltage category |
AC: II, DC: I |
|||
Pollution degree |
2 |
|||
Performance specifications |
Calculation control method |
Program storage method |
||
I/O control method |
Refresh method |
|||
Program language |
Expanded ladder, KV Script, mnemonic |
|||
Number of instructions |
Basic instruction: 81 types and 182 instructions, Application instruction: 39 types and 56 instructions, Calculation instruction: 123 types and 311 instructions, Expansion instruction: 92 types and 141 instructions, Total: 335 types and 690 instructions |
|||
Instruction execution speed |
Basic instruction: 50 ns minimum, Application instruction: 170 ns minimum |
|||
Program capacity |
8k steps |
|||
Maximum number of attachable I/O units |
8 |
|||
Maximum number of I/O points |
256 (excluding the base unit I/O) |
|||
Input relay/Output relay/Internal auxiliary relay |
R |
Total of 9600 points 1 bit (R000 to R59915) |
||
Link relay |
B |
8192 points 1 bit (B0 to B1FFF) |
||
Internal auxiliary relay |
MR |
9600 points 1 bit (MR000 to MR59915) |
||
Latch relay |
LR |
3200 points 1 bit (LR000 to LR19915) |
||
Control relay |
CR |
1440 points 1 bit (CR000 to CR8915) |
||
Timer |
T |
512 points 32 bit (T0 to T511) |
||
Counter |
C |
256 points 32 bit (C0 to C255) |
||
Data memory |
DM |
32768 points 16 bit (DM0 to DM32767) |
||
Link register |
W |
16384 points 16 bit (W0 to W3FFF) |
||
Temporary memory |
TM |
512 points 16 bit (TM0 to TM511) |
||
High-speed counter |
CTH |
2 points (CTH0 to CTH1), 32-bit automatic reset counter*5 (Input response: 100 kHz per single phase, 50 kHz per phase difference)*6 |
||
High-speed counter comparator |
CTC |
4 points (CTC0 to CTC3), 32 bits, two points per high-speed counter |
||
Index register |
Z |
12 points 32 bit (Z01 to Z12) |
||
Control memory |
CM |
9000 points 16 bit (CM0 to CM8999) |
||
Base unit I/O |
Input: 14 points, output: 10 points, Input common: 1 point, Output common: 5 points |
|||
Number of comments and labels that can be stored in the main unit |
Device comment |
20000 |
||
Label |
28000 |
|||
Power off hold function |
Program memory |
Flash ROM can be rewritten 10000 times |
||
Device |
Nonvolatile RAM*7 |
|||
Self-diagnosis function |
CPU error, RAM error, and other problems |
|||
Input specifications |
Relay number |
General input: R000 to R003, R008 to R013 (10 points), High-speed A-phase and B-phase input: R004 to R007 (2 channels, 4 points in total) |
||
Input mode |
24 VDC input (open collector) |
|||
Maximum input voltage |
26.4 VDC |
|||
Rated input voltage |
24 VDC (General input: 5.3 mA, High-speed A-phase and B-phase input: 6.5 mA*8) |
|||
Minimum ON voltage |
19 VDC |
|||
Maximum OFF current |
1.5 mA |
|||
Common method |
General input: All points/1 common (1 terminal), High-speed A-phase and B-phase input: Shared common for all points (shared with general input) |
|||
Circuit delay time |
General input: |
|||
Input time constant |
Normal: 10 ms, When the HSP instruction is used: 10 μs |
|||
Input time constant setting 10 µs: Digital filter 1.6 to 2 µs |
||||
Response frequency |
(High-speed A-phase and B-phase input) Single phase: 100 kHz, phase difference: 50 kHz, 24 V ±10%, Duty 50% |
|||
Output specifications |
Relay number |
R500 to R509 (10 points) |
||
Output mode |
Relay |
|||
Rated load |
250 VAC/30 VDC, 2 A |
|||
Common method |
2 to 4 points/1 common |
|||
ON/OFF response time |
10 ms or less |
|||
ON resistance |
50 mΩ or less |
|||
Minimum applicable load |
100 μA/100 mVDC |
|||
Relay life |
Electrical: 100000 cycles or more (20 cycles/minute), Mechanical: 20000000 cycles or more |
|||
Relay replacement |
Impossible |
|||
Built-in serial port |
Interface |
Communication standard |
RS-232C |
|
Connection |
Modular connector |
|||
Transmission specifications RS-232C |
Baud rate |
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps |
||
Transmission method |
Full duplex |
|||
Data format |
Start bit |
1 bit |
||
Data bits |
7 bits, 8 bits |
|||
Stop bits |
1 bit, 2 bits |
|||
Error detection |
Parity |
Even, odd, none |
||
Transmission distance |
15 m 49.2' |
|||
Number of transmission units |
1 |
|||
Indication |
SD (green), RD (red) |
|||
Internal current consumption |
79 VA |
|||
Weight |
Approx. 500 g |
|||
*1 The range guaranteed as a system (excluding items specially noted for the units and cassettes). |